(1) The valve does not operate.
The fault phenomenon and its causes are as follows:
1. No source of gas.① The air source is not open, ② due to the water content of the air source ice in winter, resulting in the air duct blockage or the filter, pressure relief valve blockage failure, ③ air compressor failure, ④ air source main pipe leakage.
2. Air source, no signal.① DCS output fault, ② signal cable interruption; ③ locator fault;
3. The locator has no gas source.① Filter blockage; ② pressure relief valve failure ③ pipe leakage or blockage.
4. The positioner has a gas source and no output. The nozzle is blocked.
5. Signal, no action.① Core and seat stuck, ② stem bent or broken; ③ seat core frozen or coke block dirt; ④ actuator spring rust due to long use; ⑤ valve spring broken or diaphragm damaged; ⑥ solenoid valve failure; ⑦ stem stuck.
(2) The operation of the valve is unstable.
The fault phenomenon and causes are as follows:
1. Unstable pressure of the air source. Pressure relief valve failure.
2. The signal pressure is unstable.① PID parameters of control point; ② regulator output is unstable; ③ wiring is loose.
3. The air source pressure is stable, and the signal pressure is also stable, but the action of the regulating valve is still unstable.① Locator fault; ② output pipe and line leak; ③ actuator is too rigid; large friction resistance in ④ stem movement; ⑤ working condition is unstable, the current condition does not match the selection; ⑥ diaphragm or spring is broken; ⑦ cylinder or membrane head is leaking; ⑧ valve interior is damaged; ⑨ measuring point is unstable.
(3) Valve vibration.
The fault phenomenon and causes are as follows:
1. The regulating valve vibrates at any opening degree.① Unstable support; vibration source near ②; ③ spool and bushing; severe throttling.
2. The regulating valve vibrates near the full closed position.① The regulating valve is large and often used under small opening; ② single seat valve is not suitable for working conditions.
(4) The action of the valve is slow.
The phenomenon and causes of dullness are as follows:
The valve stem is dull during the reciprocating action.① Bond blockage in the valve; ② PTFE packing deterioration hardening or graphite packing lubricating oil dry; ③ packing is too tight, the friction resistance increases; ④ large friction resistance due to the valve stem is not straight; ⑤ cylinder strength is not large enough, cylinder or gas source problems; ⑥ operating condition changes; ⑦ spring fault; ⑧ locator failure.
(5) The leakage amount of the valve increases.
The causes of the leakage are as follows:
1. Large leakage volume when the valve is fully closed.① The valve core is worn, internal leakage is serious, ② valve is not adjusted and closed; ③ mechanical zero is not adjusted.
2. The valve cannot reach the fully closed position.① The medium pressure difference is too large, the actuator torque is too small, the air source pressure is not enough, and the valve is not closed; there are foreign objects in ② valve; the ③ bushing is coking; the interior of ④ valve is damaged.
(6) The flow adjustable range is smaller.
material cause: The valve core or valve seat is corroded smaller, so that the normal opening becomes larger.
Tanggu Water Seal Valve Co., Ltd., is a technologically advanced elastic seat valve supporting enterprises, the products are elastic seat wafer butterfly valve, lug butterfly valve, double flange concentric butterfly valve, double flange eccentric butterfly valve, balance valve, wafer dual plate check valve and so on. At Tianjin Tanggu Water Seal Valve Co., Ltd., we pride ourselves on providing first-class products that meet the highest industry standards. With our wide range of valves and fittings, you can trust us to provide the perfect solution for your water system. Contact us today to learn more about our products and how we can help you.